2023/01/18 (Wednesday) Daily Trends and Statistics
HPCRC-RPP-A2-4-1

Trends and Statistics

Type:Daily
Date:2023/01/18
Day of Week:Wednesday
Coverage:100.0%
 
PQube Information

Location:HPCRC-RPP-A2-4-1
PQube ID:pqube-015
Note 1:(note not set)
Note 2:(note not set)
PQube Serial Number:P006000
Model Number:PQube 02-0000
Firmware Version:2.1.7 #2930
IP Address:128.112.176.76
 
Configuration

Power Configuration:Wye/Star
Nominal Line-to-Neutral Voltage:120V
Nominal Line-to-Line Voltage:208V
Nominal Frequency:60Hz
 
Trend Summary

2023/01/18
ChannelMinAvgMax
L-N RMS RMS (12-cyc) 118.3V 119.0V 120.1V
RMS 1/2 (1-cyc) 117.8V --- 120.3V
L1-N RMS 1/2 (1-cyc) 118.0V 119.5V 120.3V
L2-N RMS 1/2 (1-cyc) 118.5V 119.3V 119.7V
L3-N RMS 1/2 (1-cyc) 117.8V 118.5V 119.2V
N-E RMS 1/2 (1-cyc) 0.3V 0.6V 1.2V
L-L RMS RMS (12-cyc) 204.6V 206.2V 208.1V
RMS 1/2 (1-cyc) 203.9V --- 208.3V
L1-L2 RMS 1/2 (1-cyc) 205.2V 207.3V 208.3V
L2-L3 RMS 1/2 (1-cyc) 204.7V 205.5V 206.7V
L3-L1 RMS 1/2 (1-cyc) 203.9V 206.0V 206.8V
Frequency (1-cyc) 59.948Hz 59.995Hz 60.050Hz
THD-V 1.10% 1.20% 1.40%
THD-V L1 1.10% 1.10% 1.40%
THD-V L2 1.10% 1.20% 1.30%
THD-V L3 1.00% 1.20% 1.40%
Voltage Unbalance 0.10% 0.40% 0.70%
Flicker Pinst 0.00 0.02 3.01
PST 0.07 0.17 0.58
PLT 0.08 0.16 0.56
 
Cumulative Probability

2023/01/18
ChannelPercent of TimeBetween
L-N RMS 50% 118.5V~ 119.5V
95% 118.4V~ 120.0V
99% 118.3V~ 120.0V
99.5% 118.3V~ 120.0V
L-L RMS 50% 205.4V~ 206.8V
95% 205.1V~ 208.0V
99% 204.9V~ 208.0V
99.5% 204.9V~ 208.0V
Frequency (1-cyc) 50% 59.974Hz~ 60.017Hz
95% 59.965Hz~ 60.035Hz
99% 59.956Hz~ 60.044Hz
99.5% 59.956Hz~ 60.044Hz
THD-V 50% 1.15%~ 1.40%
95% 1.15%~ 1.40%
99% 1.10%~ 1.40%
99.5% 1.10%~ 1.40%
Voltage Unbalance 50% 0.25%~ 0.65%
95% 0.15%~ 0.65%
99% 0.15%~ 0.65%
99.5% 0.15%~ 0.70%
Flicker P(inst) 50% 0.00~ 0.04
95% 0.00~ 0.19
99% 0.00~ 0.71
99.5% 0.00~ 0.95
Flicker P(st) 50% 0.08~ 0.19
95% 0.08~ 0.58
99% 0.08~ 0.58
99.5% 0.08~ 0.58
Flicker P(lt) 50% 0.08~ 0.19
95% 0.08~ 0.56
99% 0.08~ 0.56
99.5% 0.08~ 0.56
 
Load Duration

2023/01/18
ChannelPercent of TimeExceeded
 

Data from the PSL PQube® by www.PowerStandards.com