2023/07/03 (Monday) Daily Trends and Statistics HPCRC-RPP-A2-4-1 Trends and Statistics -------------------- Type: Daily Date: 2023/07/03 Day of Week: Monday Coverage: 100.0% PQube Information -------------------- Location: HPCRC-RPP-A2-4-1 PQube ID: pqube-015 Note 1: (note not set) Note 2: (note not set) PQube Serial Number: P006000 Model Number: PQube 02-0000 Firmware Version: 2.1.7 #2930 IP Address: 128.112.176.76 Configuration -------------------- Power Configuration: Wye/Star Nominal Line-to-Neutral Voltage: 120V Nominal Line-to-Line Voltage: 208V Nominal Frequency: 60Hz Trend Summary -------------------- L-N RMS RMS (12-cyc)Min: 118.4V RMS (12-cyc)Avg: 119.2V RMS (12-cyc)Max: 119.9V RMS 1/2 (1-cyc) Min: 118.2V RMS 1/2 (1-cyc) Max: 120.2V L1-N RMS 1/2 (1-cyc) Min: 119.3V Avg: 119.6V Max: 120.2V L2-N RMS 1/2 (1-cyc) Min: 118.8V Avg: 119.3V Max: 119.8V L3-N RMS 1/2 (1-cyc) Min: 118.2V Avg: 118.6V Max: 118.9V N-E RMS 1/2 (1-cyc) Min: 0.3V Avg: 0.8V Max: 1.8V L-L RMS RMS (12-cyc)Min: 205.2V RMS (12-cyc)Avg: 206.4V RMS (12-cyc)Max: 208.0V RMS 1/2 (1-cyc) Min: 205.0V RMS 1/2 (1-cyc) Max: 208.2V L1-L2 RMS 1/2 (1-cyc) Min: 206.7V Avg: 207.5V Max: 208.2V L2-L3 RMS 1/2 (1-cyc) Min: 205.0V Avg: 205.6V Max: 206.2V L3-L1 RMS 1/2 (1-cyc) Min: 205.8V Avg: 206.3V Max: 206.9V Frequency (1-cyc) Min: 59.963Hz Avg: 60.003Hz Max: 60.043Hz THD-V Min: 1.30% Avg: 1.30% Max: 1.40% THD-V L1 Min: 1.20% Avg: 1.20% Max: 1.30% THD-V L2 Min: 1.20% Avg: 1.20% Max: 1.40% THD-V L3 Min: 1.30% Avg: 1.30% Max: 1.40% Voltage Unbalance Min: 0.30% Avg: 0.40% Max: 0.60% Flicker P(inst) Min: 0.00 Avg: 0.00 Max: 0.75 P(ST) Min: 0.06 Avg: 0.12 Max: 0.22 P(LT) Min: 0.07 Avg: 0.13 Max: 0.20 Cumulative Probability -------------------- L-N RMS 50%: 118.5V: 119.7V 95%: 118.4V: 119.8V 99%: 118.4V: 119.9V 99.5%: 118.4V: 119.9V L-L RMS 50%: 205.6V: 207.5V 95%: 205.4V: 207.8V 99%: 205.4V: 208.0V 99.5%: 205.2V: 208.0V Frequency (1-cyc) 50%: 59.982Hz: 60.017Hz 95%: 59.974Hz: 60.035Hz 99%: 59.965Hz: 60.043Hz 99.5%: 59.965Hz: 60.043Hz THD-V 50%: 1.35%: 1.40% 95%: 1.30%: 1.40% 99%: 1.30%: 1.40% 99.5%: 1.30%: 1.40% Voltage Unbalance 50%: 0.45%: 0.55% 95%: 0.35%: 0.60% 99%: 0.35%: 0.60% 99.5%: 0.35%: 0.60% Flicker P(inst) 50%: 0.00: 0.04 95%: 0.00: 0.08 99%: 0.00: 0.11 99.5%: 0.00: 0.15 Flicker P(st) 50%: 0.08: 0.19 95%: 0.06: 0.22 99%: 0.06: 0.22 99.5%: 0.06: 0.22 Flicker P(lt) 50%: 0.08: 0.19 95%: 0.07: 0.20 99%: 0.07: 0.20 99.5%: 0.07: 0.20 Load Duration -------------------- -------------------- Made with the PQube(R) by Power Standards Lab (www.PowerStandards.com)