2023/12/25 (Monday) Daily Trends and Statistics HPCRC-RPP-A2-4-1 Trends and Statistics -------------------- Type: Daily Date: 2023/12/25 Day of Week: Monday Coverage: 100.0% PQube Information -------------------- Location: HPCRC-RPP-A2-4-1 PQube ID: pqube-015 Note 1: (note not set) Note 2: (note not set) PQube Serial Number: P006000 Model Number: PQube 02-0000 Firmware Version: 2.1.7 #2930 IP Address: 128.112.176.76 Configuration -------------------- Power Configuration: Wye/Star Nominal Line-to-Neutral Voltage: 120V Nominal Line-to-Line Voltage: 208V Nominal Frequency: 60Hz Trend Summary -------------------- L-N RMS RMS (12-cyc)Min: 117.9V RMS (12-cyc)Avg: 118.7V RMS (12-cyc)Max: 119.8V RMS 1/2 (1-cyc) Min: 117.6V RMS 1/2 (1-cyc) Max: 119.9V L1-N RMS 1/2 (1-cyc) Min: 118.3V Avg: 119.0V Max: 119.9V L2-N RMS 1/2 (1-cyc) Min: 117.8V Avg: 118.6V Max: 119.4V L3-N RMS 1/2 (1-cyc) Min: 117.6V Avg: 118.7V Max: 119.5V N-E RMS 1/2 (1-cyc) Min: 0.4V Avg: 0.8V Max: 1.6V L-L RMS RMS (12-cyc)Min: 204.5V RMS (12-cyc)Avg: 205.7V RMS (12-cyc)Max: 207.5V RMS 1/2 (1-cyc) Min: 203.7V RMS 1/2 (1-cyc) Max: 207.6V L1-L2 RMS 1/2 (1-cyc) Min: 204.7V Avg: 205.8V Max: 207.6V L2-L3 RMS 1/2 (1-cyc) Min: 203.7V Avg: 205.2V Max: 206.5V L3-L1 RMS 1/2 (1-cyc) Min: 204.6V Avg: 206.1V Max: 207.4V Frequency (1-cyc) Min: 59.963Hz Avg: 60.004Hz Max: 60.040Hz THD-V Min: 1.10% Avg: 1.20% Max: 1.40% THD-V L1 Min: 1.10% Avg: 1.10% Max: 1.40% THD-V L2 Min: 1.10% Avg: 1.10% Max: 1.40% THD-V L3 Min: 1.10% Avg: 1.10% Max: 1.40% Voltage Unbalance Min: 0.00% Avg: 0.10% Max: 0.60% Flicker P(inst) Min: 0.00 Avg: 0.06 Max: 1.93 P(ST) Min: 0.28 Avg: 0.35 Max: 0.42 P(LT) Min: 0.29 Avg: 0.36 Max: 0.41 Cumulative Probability -------------------- L-N RMS 50%: 118.5V: 119.0V 95%: 118.4V: 119.3V 99%: 118.3V: 119.4V 99.5%: 118.3V: 119.5V L-L RMS 50%: 205.1V: 206.1V 95%: 204.9V: 206.6V 99%: 204.9V: 206.6V 99.5%: 204.7V: 206.8V Frequency (1-cyc) 50%: 59.991Hz: 60.017Hz 95%: 59.974Hz: 60.035Hz 99%: 59.974Hz: 60.035Hz 99.5%: 59.974Hz: 60.035Hz THD-V 50%: 1.25%: 1.35% 95%: 1.15%: 1.40% 99%: 1.10%: 1.40% 99.5%: 1.10%: 1.40% Voltage Unbalance 50%: 0.05%: 0.35% 95%: 0.05%: 0.35% 99%: 0.00%: 0.45% 99.5%: 0.00%: 0.45% Flicker P(inst) 50%: 0.00: 0.11 95%: 0.00: 0.43 99%: 0.00: 0.67 99.5%: 0.00: 0.83 Flicker P(st) 50%: 0.28: 0.42 95%: 0.28: 0.42 99%: 0.28: 0.42 99.5%: 0.28: 0.42 Flicker P(lt) 50%: 0.29: 0.41 95%: 0.29: 0.41 99%: 0.29: 0.41 99.5%: 0.29: 0.41 Load Duration -------------------- -------------------- Made with the PQube(R) by Power Standards Lab (www.PowerStandards.com)