2024/03/16 (Saturday) Daily Trends and Statistics
HPCRC-RPP-A2-4-1

Trends and Statistics

Type:Daily
Date:2024/03/16
Day of Week:Saturday
Coverage:100.0%
 
PQube Information

Location:HPCRC-RPP-A2-4-1
PQube ID:pqube-015
Note 1:(note not set)
Note 2:(note not set)
PQube Serial Number:P006000
Model Number:PQube 02-0000
Firmware Version:2.1.7 #2930
IP Address:128.112.176.76
 
Configuration

Power Configuration:Wye/Star
Nominal Line-to-Neutral Voltage:120V
Nominal Line-to-Line Voltage:208V
Nominal Frequency:60Hz
 
Trend Summary

2024/03/16
ChannelMinAvgMax
L-N RMS RMS (12-cyc) 118.4V 119.2V 120.1V
RMS 1/2 (1-cyc) 118.0V --- 120.3V
L1-N RMS 1/2 (1-cyc) 119.3V 119.7V 120.3V
L2-N RMS 1/2 (1-cyc) 118.6V 119.3V 119.8V
L3-N RMS 1/2 (1-cyc) 118.0V 118.5V 119.0V
N-E RMS 1/2 (1-cyc) 0.3V 0.7V 1.4V
L-L RMS RMS (12-cyc) 205.2V 206.5V 208.1V
RMS 1/2 (1-cyc) 204.4V --- 208.4V
L1-L2 RMS 1/2 (1-cyc) 206.6V 207.5V 208.4V
L2-L3 RMS 1/2 (1-cyc) 204.4V 205.5V 206.4V
L3-L1 RMS 1/2 (1-cyc) 205.8V 206.3V 206.9V
Frequency (1-cyc) 59.948Hz 60.004Hz 60.046Hz
THD-V 1.30% 1.30% 1.50%
THD-V L1 1.10% 1.10% 1.30%
THD-V L2 1.30% 1.30% 1.40%
THD-V L3 1.30% 1.30% 1.50%
Voltage Unbalance 0.40% 0.40% 0.70%
Flicker Pinst 0.00 0.01 1.00
PST 0.07 0.13 0.20
PLT 0.08 0.13 0.18
 
Cumulative Probability

2024/03/16
ChannelPercent of TimeBetween
L-N RMS 50% 118.5V~ 119.7V
95% 118.4V~ 120.0V
99% 118.4V~ 120.0V
99.5% 118.4V~ 120.1V
L-L RMS 50% 205.4V~ 207.5V
95% 205.4V~ 208.0V
99% 205.2V~ 208.0V
99.5% 205.2V~ 208.0V
Frequency (1-cyc) 50% 59.982Hz~ 60.026Hz
95% 59.965Hz~ 60.035Hz
99% 59.956Hz~ 60.044Hz
99.5% 59.956Hz~ 60.044Hz
THD-V 50% 1.35%~ 1.45%
95% 1.30%~ 1.50%
99% 1.30%~ 1.50%
99.5% 1.30%~ 1.50%
Voltage Unbalance 50% 0.45%~ 0.55%
95% 0.40%~ 0.65%
99% 0.40%~ 0.65%
99.5% 0.40%~ 0.65%
Flicker P(inst) 50% 0.00~ 0.04
95% 0.00~ 0.08
99% 0.00~ 0.11
99.5% 0.00~ 0.11
Flicker P(st) 50% 0.08~ 0.19
95% 0.08~ 0.19
99% 0.08~ 0.19
99.5% 0.08~ 0.20
Flicker P(lt) 50% 0.08~ 0.18
95% 0.08~ 0.18
99% 0.08~ 0.18
99.5% 0.08~ 0.18
 
Load Duration

2024/03/16
ChannelPercent of TimeExceeded
 

Data from the PSL PQube® by www.PowerStandards.com