2024/03/28 (Thursday) Daily Trends and Statistics
HPCRC-RPP-A2-4-1

Trends and Statistics

Type:Daily
Date:2024/03/28
Day of Week:Thursday
Coverage:100.0%
 
PQube Information

Location:HPCRC-RPP-A2-4-1
PQube ID:pqube-015
Note 1:(note not set)
Note 2:(note not set)
PQube Serial Number:P006000
Model Number:PQube 02-0000
Firmware Version:2.1.7 #2930
IP Address:128.112.176.76
 
Configuration

Power Configuration:Wye/Star
Nominal Line-to-Neutral Voltage:120V
Nominal Line-to-Line Voltage:208V
Nominal Frequency:60Hz
 
Trend Summary

2024/03/28
ChannelMinAvgMax
L-N RMS RMS (12-cyc) 117.9V 118.9V 119.9V
RMS 1/2 (1-cyc) 117.8V --- 120.1V
L1-N RMS 1/2 (1-cyc) 119.2V 119.6V 120.1V
L2-N RMS 1/2 (1-cyc) 118.4V 118.9V 119.5V
L3-N RMS 1/2 (1-cyc) 117.8V 118.2V 118.7V
N-E RMS 1/2 (1-cyc) 0.4V 0.8V 1.6V
L-L RMS RMS (12-cyc) 204.4V 206.0V 207.8V
RMS 1/2 (1-cyc) 204.0V --- 207.9V
L1-L2 RMS 1/2 (1-cyc) 206.3V 207.1V 207.9V
L2-L3 RMS 1/2 (1-cyc) 204.0V 204.8V 205.5V
L3-L1 RMS 1/2 (1-cyc) 205.4V 206.1V 206.9V
Frequency (1-cyc) 59.939Hz 59.998Hz 60.053Hz
THD-V 1.20% 1.20% 1.60%
THD-V L1 1.10% 1.10% 1.50%
THD-V L2 1.20% 1.20% 1.60%
THD-V L3 1.20% 1.20% 1.60%
Voltage Unbalance 0.40% 0.40% 0.80%
Flicker Pinst 0.00 0.00 0.33
PST 0.07 0.09 0.14
PLT 0.07 0.09 0.12
 
Cumulative Probability

2024/03/28
ChannelPercent of TimeBetween
L-N RMS 50% 118.4V~ 119.7V
95% 118.1V~ 119.7V
99% 117.9V~ 119.8V
99.5% 117.9V~ 119.8V
L-L RMS 50% 204.9V~ 207.3V
95% 204.4V~ 207.5V
99% 204.4V~ 207.8V
99.5% 204.4V~ 207.8V
Frequency (1-cyc) 50% 59.982Hz~ 60.017Hz
95% 59.956Hz~ 60.035Hz
99% 59.956Hz~ 60.044Hz
99.5% 59.948Hz~ 60.044Hz
THD-V 50% 1.25%~ 1.35%
95% 1.20%~ 1.45%
99% 1.20%~ 1.45%
99.5% 1.20%~ 1.45%
Voltage Unbalance 50% 0.45%~ 0.55%
95% 0.40%~ 0.75%
99% 0.40%~ 0.75%
99.5% 0.40%~ 0.75%
Flicker P(inst) 50% 0.00~ 0.04
95% 0.00~ 0.04
99% 0.00~ 0.08
99.5% 0.00~ 0.08
Flicker P(st) 50% 0.08~ 0.11
95% 0.07~ 0.14
99% 0.07~ 0.14
99.5% 0.07~ 0.14
Flicker P(lt) 50% 0.08~ 0.11
95% 0.07~ 0.12
99% 0.07~ 0.12
99.5% 0.07~ 0.12
 
Load Duration

2024/03/28
ChannelPercent of TimeExceeded
 

Data from the PSL PQube® by www.PowerStandards.com