2024/07/07 (Sunday) Daily Trends and Statistics
HPCRC-RPP-A2-4-1

Trends and Statistics

Type:Daily
Date:2024/07/07
Day of Week:Sunday
Coverage:100.0%
 
PQube Information

Location:HPCRC-RPP-A2-4-1
PQube ID:pqube-015
Note 1:(note not set)
Note 2:(note not set)
PQube Serial Number:P006000
Model Number:PQube 02-0000
Firmware Version:2.1.7 #2930
IP Address:128.112.176.76
 
Configuration

Power Configuration:Wye/Star
Nominal Line-to-Neutral Voltage:120V
Nominal Line-to-Line Voltage:208V
Nominal Frequency:60Hz
 
Trend Summary

2024/07/07
ChannelMinAvgMax
L-N RMS RMS (12-cyc) 117.9V 118.7V 119.8V
RMS 1/2 (1-cyc) 117.7V --- 119.9V
L1-N RMS 1/2 (1-cyc) 118.8V 119.3V 119.9V
L2-N RMS 1/2 (1-cyc) 118.2V 118.8V 119.3V
L3-N RMS 1/2 (1-cyc) 117.7V 118.3V 118.9V
N-E RMS 1/2 (1-cyc) 0.4V 0.9V 1.7V
L-L RMS RMS (12-cyc) 204.1V 205.8V 207.2V
RMS 1/2 (1-cyc) 203.8V --- 207.4V
L1-L2 RMS 1/2 (1-cyc) 205.8V 206.6V 207.4V
L2-L3 RMS 1/2 (1-cyc) 203.8V 204.9V 205.7V
L3-L1 RMS 1/2 (1-cyc) 205.0V 205.9V 206.8V
Frequency (1-cyc) 59.951Hz 59.992Hz 60.043Hz
THD-V 1.10% 1.20% 1.40%
THD-V L1 1.10% 1.10% 1.30%
THD-V L2 1.10% 1.10% 1.40%
THD-V L3 1.10% 1.10% 1.40%
Voltage Unbalance 0.20% 0.30% 0.70%
Flicker Pinst 0.00 0.00 1.19
PST 0.07 0.11 0.31
PLT 0.07 0.11 0.28
 
Cumulative Probability

2024/07/07
ChannelPercent of TimeBetween
L-N RMS 50% 118.4V~ 119.3V
95% 118.1V~ 119.6V
99% 117.9V~ 119.6V
99.5% 117.9V~ 119.6V
L-L RMS 50% 204.9V~ 206.6V
95% 204.4V~ 206.8V
99% 204.2V~ 207.0V
99.5% 204.2V~ 207.0V
Frequency (1-cyc) 50% 59.974Hz~ 60.009Hz
95% 59.956Hz~ 60.035Hz
99% 59.956Hz~ 60.035Hz
99.5% 59.956Hz~ 60.035Hz
THD-V 50% 1.15%~ 1.25%
95% 1.10%~ 1.35%
99% 1.10%~ 1.35%
99.5% 1.10%~ 1.35%
Voltage Unbalance 50% 0.25%~ 0.55%
95% 0.25%~ 0.55%
99% 0.25%~ 0.65%
99.5% 0.20%~ 0.65%
Flicker P(inst) 50% 0.00~ 0.04
95% 0.00~ 0.08
99% 0.00~ 0.15
99.5% 0.00~ 0.19
Flicker P(st) 50% 0.08~ 0.11
95% 0.07~ 0.31
99% 0.07~ 0.31
99.5% 0.07~ 0.31
Flicker P(lt) 50% 0.08~ 0.11
95% 0.07~ 0.28
99% 0.07~ 0.28
99.5% 0.07~ 0.28
 
Load Duration

2024/07/07
ChannelPercent of TimeExceeded
 

Data from the PSL PQube® by www.PowerStandards.com