2024/07/17 (Wednesday) Daily Trends and Statistics
HPCRC-RPP-A2-4-1

Trends and Statistics

Type:Daily
Date:2024/07/17
Day of Week:Wednesday
Coverage:100.0%
 
PQube Information

Location:HPCRC-RPP-A2-4-1
PQube ID:pqube-015
Note 1:(note not set)
Note 2:(note not set)
PQube Serial Number:P006000
Model Number:PQube 02-0000
Firmware Version:2.1.7 #2930
IP Address:128.112.176.76
 
Configuration

Power Configuration:Wye/Star
Nominal Line-to-Neutral Voltage:120V
Nominal Line-to-Line Voltage:208V
Nominal Frequency:60Hz
 
Trend Summary

2024/07/17
ChannelMinAvgMax
L-N RMS RMS (12-cyc) 117.6V 118.4V 119.5V
RMS 1/2 (1-cyc) 116.8V --- 119.7V
L1-N RMS 1/2 (1-cyc) 117.7V 118.7V 119.7V
L2-N RMS 1/2 (1-cyc) 117.2V 118.2V 119.4V
L3-N RMS 1/2 (1-cyc) 116.8V 118.2V 119.1V
N-E RMS 1/2 (1-cyc) 0.4V 0.9V 1.7V
L-L RMS RMS (12-cyc) 203.6V 205.1V 207.1V
RMS 1/2 (1-cyc) 202.4V --- 207.3V
L1-L2 RMS 1/2 (1-cyc) 203.7V 205.3V 207.3V
L2-L3 RMS 1/2 (1-cyc) 202.4V 204.6V 206.2V
L3-L1 RMS 1/2 (1-cyc) 203.5V 205.4V 206.9V
Frequency (1-cyc) 59.957Hz 60.002Hz 60.043Hz
THD-V 1.00% 1.10% 1.40%
THD-V L1 1.00% 1.10% 1.40%
THD-V L2 1.00% 1.00% 1.40%
THD-V L3 1.00% 1.10% 1.30%
Voltage Unbalance 0.00% 0.10% 0.70%
Flicker Pinst 0.00 0.05 4.30
PST 0.12 0.31 0.52
PLT 0.18 0.32 0.47
 
Cumulative Probability

2024/07/17
ChannelPercent of TimeBetween
L-N RMS 50% 118.2V~ 118.7V
95% 117.9V~ 119.1V
99% 117.8V~ 119.3V
99.5% 117.8V~ 119.3V
L-L RMS 50% 204.7V~ 205.6V
95% 204.2V~ 206.3V
99% 204.0V~ 206.6V
99.5% 204.0V~ 206.8V
Frequency (1-cyc) 50% 59.982Hz~ 60.017Hz
95% 59.974Hz~ 60.035Hz
99% 59.965Hz~ 60.035Hz
99.5% 59.957Hz~ 60.043Hz
THD-V 50% 1.15%~ 1.25%
95% 1.05%~ 1.35%
99% 1.05%~ 1.35%
99.5% 1.05%~ 1.35%
Voltage Unbalance 50% 0.05%~ 0.35%
95% 0.00%~ 0.45%
99% 0.00%~ 0.55%
99.5% 0.00%~ 0.55%
Flicker P(inst) 50% 0.00~ 0.04
95% 0.00~ 0.39
99% 0.00~ 0.75
99.5% 0.00~ 0.95
Flicker P(st) 50% 0.19~ 0.43
95% 0.12~ 0.51
99% 0.12~ 0.51
99.5% 0.12~ 0.51
Flicker P(lt) 50% 0.23~ 0.39
95% 0.18~ 0.47
99% 0.18~ 0.47
99.5% 0.18~ 0.47
 
Load Duration

2024/07/17
ChannelPercent of TimeExceeded
 

Data from the PSL PQube® by www.PowerStandards.com