2024/08/11 (Sunday) Daily Trends and Statistics
HPCRC-RPP-A2-4-1

Trends and Statistics

Type:Daily
Date:2024/08/11
Day of Week:Sunday
Coverage:100.0%
 
PQube Information

Location:HPCRC-RPP-A2-4-1
PQube ID:pqube-015
Note 1:(note not set)
Note 2:(note not set)
PQube Serial Number:P006000
Model Number:PQube 02-0000
Firmware Version:2.1.7 #2930
IP Address:128.112.176.76
 
Configuration

Power Configuration:Wye/Star
Nominal Line-to-Neutral Voltage:120V
Nominal Line-to-Line Voltage:208V
Nominal Frequency:60Hz
 
Trend Summary

2024/08/11
ChannelMinAvgMax
L-N RMS RMS (12-cyc) 117.1V 118.4V 120.0V
RMS 1/2 (1-cyc) 116.5V --- 120.2V
L1-N RMS 1/2 (1-cyc) 117.5V 118.8V 120.2V
L2-N RMS 1/2 (1-cyc) 117.2V 118.6V 119.7V
L3-N RMS 1/2 (1-cyc) 116.5V 118.0V 118.9V
N-E RMS 1/2 (1-cyc) 0.4V 0.9V 1.6V
L-L RMS RMS (12-cyc) 203.6V 205.2V 208.4V
RMS 1/2 (1-cyc) 202.6V --- 208.8V
L1-L2 RMS 1/2 (1-cyc) 203.5V 206.0V 208.8V
L2-L3 RMS 1/2 (1-cyc) 202.6V 204.6V 206.2V
L3-L1 RMS 1/2 (1-cyc) 202.9V 205.0V 206.9V
Frequency (1-cyc) 59.951Hz 60.003Hz 60.043Hz
THD-V 1.00% 1.10% 1.40%
THD-V L1 1.00% 1.10% 1.40%
THD-V L2 1.00% 1.10% 1.40%
THD-V L3 1.00% 1.10% 1.40%
Voltage Unbalance 0.00% 0.30% 1.30%
Flicker Pinst 0.00 0.16 4.79
PST 0.07 0.50 0.79
PLT 0.24 0.51 0.70
 
Cumulative Probability

2024/08/11
ChannelPercent of TimeBetween
L-N RMS 50% 118.1V~ 118.9V
95% 117.8V~ 119.5V
99% 117.7V~ 119.7V
99.5% 117.7V~ 119.7V
L-L RMS 50% 204.7V~ 205.9V
95% 204.2V~ 207.5V
99% 204.0V~ 207.8V
99.5% 204.0V~ 207.8V
Frequency (1-cyc) 50% 59.982Hz~ 60.017Hz
95% 59.965Hz~ 60.035Hz
99% 59.965Hz~ 60.035Hz
99.5% 59.956Hz~ 60.043Hz
THD-V 50% 1.15%~ 1.25%
95% 1.05%~ 1.35%
99% 1.05%~ 1.35%
99.5% 1.05%~ 1.35%
Voltage Unbalance 50% 0.15%~ 0.45%
95% 0.05%~ 0.85%
99% 0.05%~ 0.95%
99.5% 0.05%~ 0.95%
Flicker P(inst) 50% 0.00~ 0.19
95% 0.00~ 1.03
99% 0.00~ 1.51
99.5% 0.00~ 1.71
Flicker P(st) 50% 0.39~ 0.63
95% 0.16~ 0.75
99% 0.07~ 0.79
99.5% 0.07~ 0.79
Flicker P(lt) 50% 0.39~ 0.63
95% 0.27~ 0.70
99% 0.27~ 0.70
99.5% 0.27~ 0.70
 
Load Duration

2024/08/11
ChannelPercent of TimeExceeded
 

Data from the PSL PQube® by www.PowerStandards.com