2024/08/17 (Saturday) Daily Trends and Statistics
HPCRC-RPP-A2-4-1

Trends and Statistics

Type:Daily
Date:2024/08/17
Day of Week:Saturday
Coverage:100.0%
 
PQube Information

Location:HPCRC-RPP-A2-4-1
PQube ID:pqube-015
Note 1:(note not set)
Note 2:(note not set)
PQube Serial Number:P006000
Model Number:PQube 02-0000
Firmware Version:2.1.7 #2930
IP Address:128.112.176.76
 
Configuration

Power Configuration:Wye/Star
Nominal Line-to-Neutral Voltage:120V
Nominal Line-to-Line Voltage:208V
Nominal Frequency:60Hz
 
Trend Summary

2024/08/17
ChannelMinAvgMax
L-N RMS RMS (12-cyc) 117.6V 118.3V 119.6V
RMS 1/2 (1-cyc) 116.5V --- 119.8V
L1-N RMS 1/2 (1-cyc) 117.8V 118.6V 119.8V
L2-N RMS 1/2 (1-cyc) 117.2V 118.0V 119.2V
L3-N RMS 1/2 (1-cyc) 116.5V 118.2V 119.1V
N-E RMS 1/2 (1-cyc) 0.5V 1.0V 1.8V
L-L RMS RMS (12-cyc) 203.4V 204.9V 207.0V
RMS 1/2 (1-cyc) 202.3V --- 207.2V
L1-L2 RMS 1/2 (1-cyc) 203.7V 205.0V 207.2V
L2-L3 RMS 1/2 (1-cyc) 202.3V 204.3V 205.8V
L3-L1 RMS 1/2 (1-cyc) 203.4V 205.3V 206.9V
Frequency (1-cyc) 59.948Hz 60.000Hz 60.043Hz
THD-V 1.00% 1.10% 1.40%
THD-V L1 1.00% 1.10% 1.30%
THD-V L2 1.00% 1.10% 1.40%
THD-V L3 1.00% 1.10% 1.40%
Voltage Unbalance 0.00% 0.10% 0.60%
Flicker Pinst 0.00 0.03 4.62
PST 0.21 0.27 0.33
PLT 0.24 0.28 0.34
 
Cumulative Probability

2024/08/17
ChannelPercent of TimeBetween
L-N RMS 50% 117.9V~ 118.7V
95% 117.8V~ 118.9V
99% 117.7V~ 119.1V
99.5% 117.7V~ 119.4V
L-L RMS 50% 204.4V~ 205.4V
95% 203.7V~ 206.1V
99% 203.7V~ 206.3V
99.5% 203.7V~ 206.6V
Frequency (1-cyc) 50% 59.982Hz~ 60.017Hz
95% 59.965Hz~ 60.035Hz
99% 59.956Hz~ 60.035Hz
99.5% 59.956Hz~ 60.043Hz
THD-V 50% 1.15%~ 1.25%
95% 1.05%~ 1.35%
99% 1.05%~ 1.35%
99.5% 1.05%~ 1.35%
Voltage Unbalance 50% 0.05%~ 0.35%
95% 0.05%~ 0.45%
99% 0.05%~ 0.55%
99.5% 0.00%~ 0.55%
Flicker P(inst) 50% 0.00~ 0.04
95% 0.00~ 0.23
99% 0.00~ 0.43
99.5% 0.00~ 0.51
Flicker P(st) 50% 0.27~ 0.31
95% 0.21~ 0.33
99% 0.21~ 0.33
99.5% 0.21~ 0.33
Flicker P(lt) 50% 0.27~ 0.31
95% 0.24~ 0.34
99% 0.24~ 0.34
99.5% 0.24~ 0.34
 
Load Duration

2024/08/17
ChannelPercent of TimeExceeded
 

Data from the PSL PQube® by www.PowerStandards.com