2024/08/29 (Thursday) Daily Trends and Statistics
HPCRC-RPP-A2-4-1

Trends and Statistics

Type:Daily
Date:2024/08/29
Day of Week:Thursday
Coverage:100.0%
 
PQube Information

Location:HPCRC-RPP-A2-4-1
PQube ID:pqube-015
Note 1:(note not set)
Note 2:(note not set)
PQube Serial Number:P006000
Model Number:PQube 02-0000
Firmware Version:2.1.7 #2930
IP Address:128.112.176.76
 
Configuration

Power Configuration:Wye/Star
Nominal Line-to-Neutral Voltage:120V
Nominal Line-to-Line Voltage:208V
Nominal Frequency:60Hz
 
Trend Summary

2024/08/29
ChannelMinAvgMax
L-N RMS RMS (12-cyc) 117.7V 118.9V 120.0V
RMS 1/2 (1-cyc) 116.0V --- 120.9V
L1-N RMS 1/2 (1-cyc) 118.2V 119.7V 120.9V
L2-N RMS 1/2 (1-cyc) 117.1V 119.0V 120.2V
L3-N RMS 1/2 (1-cyc) 116.0V 117.9V 119.1V
N-E RMS 1/2 (1-cyc) 0.4V 0.8V 1.6V
L-L RMS RMS (12-cyc) 203.9V 205.9V 208.1V
RMS 1/2 (1-cyc) 201.0V --- 209.4V
L1-L2 RMS 1/2 (1-cyc) 204.7V 207.5V 209.4V
L2-L3 RMS 1/2 (1-cyc) 201.0V 204.4V 206.3V
L3-L1 RMS 1/2 (1-cyc) 203.1V 205.8V 207.8V
Frequency (1-cyc) 59.945Hz 60.002Hz 60.077Hz
THD-V 1.20% 1.20% 5.80%
THD-V L1 1.10% 1.10% 5.80%
THD-V L2 1.10% 1.10% 5.70%
THD-V L3 1.20% 1.20% 5.60%
Voltage Unbalance 0.50% 0.70% 1.00%
Flicker Pinst 0.00 0.00 8.46
PST 0.06 0.11 0.39
PLT 0.08 0.12 0.29
 
Cumulative Probability

2024/08/29
ChannelPercent of TimeBetween
L-N RMS 50% 117.9V~ 119.7V
95% 117.8V~ 120.0V
99% 117.7V~ 120.0V
99.5% 117.7V~ 120.0V
L-L RMS 50% 204.4V~ 207.5V
95% 204.2V~ 208.0V
99% 204.0V~ 208.0V
99.5% 204.0V~ 208.0V
Frequency (1-cyc) 50% 59.982Hz~ 60.017Hz
95% 59.965Hz~ 60.035Hz
99% 59.956Hz~ 60.035Hz
99.5% 59.956Hz~ 60.044Hz
THD-V 50% 1.25%~ 1.35%
95% 1.20%~ 1.45%
99% 1.20%~ 1.45%
99.5% 1.20%~ 1.45%
Voltage Unbalance 50% 0.75%~ 0.85%
95% 0.55%~ 0.95%
99% 0.55%~ 0.95%
99.5% 0.50%~ 0.95%
Flicker P(inst) 50% 0.00~ 0.04
95% 0.00~ 0.08
99% 0.00~ 0.19
99.5% 0.00~ 0.23
Flicker P(st) 50% 0.08~ 0.11
95% 0.06~ 0.31
99% 0.06~ 0.31
99.5% 0.06~ 0.31
Flicker P(lt) 50% 0.08~ 0.11
95% 0.08~ 0.29
99% 0.08~ 0.29
99.5% 0.08~ 0.29
 
Load Duration

2024/08/29
ChannelPercent of TimeExceeded
 

Data from the PSL PQube® by www.PowerStandards.com